Section 6
Local HMI engineering
6.3
100
The single line diagram screen can display different values, with the
help of the dynamic text fields. Please remember that these values are
displayed by default in SI units (for example - active power is
displayed in W). Modify Scale Factor in the object properties (see
Figure
74) to display values in more readable units (for example MW).
Be sure to write the proper unit under the Unit Text field.
As the function delivers angles in radians, a scale factor of 180/pi =
57.3 shall be used to display the angle in degrees
GUID-CA49988A-9B92-4097-903C-75CEA020CBA4 V1 EN
Figure 74:
GDE: Object properties window for unit change
Events and indications
To get IED events to the LHMI event list and indications for the Start and Trip
protection indicator LEDs, the disturbance rerecorder needs to be engineered.
See the technical manual for more information on how to configure
and set the binary signals of the disturbance recorder.
IEC10000174.vsd
1MRS756800 F
630 series
Engineering Manual