Section 7
IEC 61850 communication engineering
126
GUID-2DC9FFE2-8C7E-4A9E-AEBD-2983F5D174D2 V1 EN
Figure 98:
GCB client editor
The rows of the GCB client editor show GCBs, that is, senders and the columns show
the IEDs available as GOOSE clients, that is, receivers. If the client IED is not on the
same subnetwork as the GCB sender, it cannot be configured as a client.
Different keys can be used when editing the cells.
PLUS SIGN (+), asterisk (*) or X key to add an additional client to the existing
ones
MINUS SIGN (-), SPACEBAR or DELETE to delete existing clients
Double-clicking with the mouse to add or delete clients
Upon adding or removing clients, the corresponding input sections are updated
automatically.
1MRS756800 F
630 series
Engineering Manual