1MRS756800 F
630 series
Engineering Manual
GUID-50252C85-F6EA-4B18-BFCC-97C19F5B746F V1 EN
Figure 57:
Local HMI: Placement of local HMI operation elements
Function block LEDGEN
Handles an external acknowledge signal as source to acknowledge the LEDs.
Generates an additional pulse for general purposes whenever the LEDs are
acknowledged by the operator.
Generates a pulse whenever a new LED signal occurs. It may be used to trigger
an acoustical alarm.
Handles the timer tReset and tMax for the LED operation mode 'LatchedReset-S'.
Function block GRP1_LED1 to GRP3_LED15
The 15 LEDs on the right side of the display can indicate in total 45 alarms,
warnings or other signals to the operator. They are organized in three groups 1 to
3.
Each signal group belongs to one function block.
Each LED illuminates in one of the three colors: RED, YELLOW or GREEN.
The organization of flashing, acknowledgment and group selection is done
directly between the function blocks and the basic LHMI keys, the 'Multifunction'
Section 6