IO-Link Master with PROFINET Interface StandardLine 8 Ports IP 65 / IP 66 / IP 67
Parameter
Description
[Vendor ID (VID)]
ID of the manufacturer that is to be
validated
[Device ID]
ID of the IO-Link device that is to be
validated
[IO-Link Events]
Enable / disable the transmission of
IO-Link events
* ... settings are only valid if [Fail Safe Mode] = Fail Safe with Pattern
If the parameter values of an IO-Link device are changed with IO_LINK_DEVICE, the backup
mechanism remains ineffective. The changed parameter values are not stored on the IO-Link
master.
52
Possible values
Type compatible V1.1
IO-Link device is compatible with
device with Restore
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
The IO-Link master stores the
parameter values of the connected
IO-Link device once if the data
memory of the AL1102 is empty.
When connecting an IO-Link device
with factory settings, the parameter
values stored in the IO-Link master
are restored automatically on the
IO-Link device.
0 ... 65535
ID of the manufacturer of the IO-Link
device (ifm electronic: 310)
0 ... 16777215
ID of the IO-Link device
Diabled
IO-Link won't be transmitted
Enabled
IO-Link events will be transmitted