1 Preliminary note ► Instruction > Reaction, result Important note Non-compliance can result in malfunction or interference� Information Supplementary note� 2 Safety instructions • Please read the operating instructions prior to set-up of the device� Ensure that the product is suitable for your application without any restrictions� •...
4 Installation ► Disconnect the system from power before installation� ► For installation choose a flat mounting surface� The entire bottom of the module must lie flat on the mounting surface� ► Screw the lower part onto the mounting surface using M4 screws and washers (1)�...
Page 5
ye (AS-i) bk (AUX) 1: M4 screws and washers (not supplied with the device)� Tightening torque 1�8 Nm� 2: M3�5 screws supplied� Tightening torque 1�2���1�4 Nm� 3: Functional earth springs 4: M4���M5 screw and washer (not supplied with the device)� Tightening torque max�...
The switch-on and switch-off capacity for triggering solenoids is rated up to 20 W (IEC 947-5-2, utilisation category DC-13)� Recommendation: For inductive loads use a free wheel diode on the load� ifm elec- tronic offers valve plugs with integrated free wheel diodes�...
AC2486 4 inputs / AS-i profile S-0�A�E / extended addressing mode: yes Data bit Input Socket I-1/2 I-1/2 I-3/4 I-3/4 Y-circuit inputs I-1/2 Inputs 1: sensor supply L+ 2+4: data input I-3/4 3: sensor supply L- 5: functional earth If a slave with the ID code "A" (option of extended addressing mode) is connected to a master of the first generation (version 2�0), the parameter P3 must be 1 and the output bit D3 = 0*�...
LED IR addressing: infrared receiver Overload and short circuit of the input supply and the outputs are signalled as periph- eral fault to the AS-i master (version 2�1 or higher)� 10 Technical data Technical data and further information at www�ifm�com�...