WAGO-I/O-SYSTEM 750
750-880 ETHERNET Programmable Fieldbus
3.
Enter a name for the ETHERNET link in the Name field.
4.
Select the "Tcp/Ip 3S Tcp/Ip driver" and confirm your input by clicking
[OK].
Figure 46: New communication channel via ETHERNET
5.
Double-click on the address field localhost in the column "Value" in the
"Communication parameters" dialog box.
6.
Here, enter the IP address of your fieldbus controller "192.168.1.100" and
confirm this using [Enter].
You do not need to make any changes to the other parameters (Port,
Motorola byteorder) or to the gateway settings. Confirm your input by
clicking [OK].
Figure 47: ETHERNET communication parameters
Quickstart Reference
Version 1.0.0
Application example: Starterkit880_App1_FUP.pro
43