Main Menu - Analog In/Out - Group - Danfoss VLT Programming Manual

Hvac drive
Hide thumbs Also See for VLT:
Table of Contents

Advertisement

Parameter Description

3.8 Main Menu - Analog In/Out - Group 6

3.8.1 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The frequency converter is equipped with 2 analog inputs:
3
3
Terminal 53 and 54. The analog inputs can freely be
allocated to either voltage (0 - 10 V) or current input (0/4 - 20
mA)
NOTE
Thermistors may be connected to either an analog or a
digital input.
6-00 Live Zero Timeout Time
Range:
10 s
[1 -
*
99 s]
6-01 Live Zero Timeout Function
Option:
[0]
Off
*
[1]
Freeze
output
68
Function:
Enter the Live Zero Time-out time period. Live Zero
Time-out Time is active for analog inputs, i.e.
terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value
associated with the selected current input falls
below 50% of the value set in 6-10 Terminal 53 Low
Voltage, 6-12 Terminal 53 Low Current, 6-20 Terminal
54 Low Voltage or 6-22 Terminal 54 Low Current for a
time period longer than the time set in 6-00 Live
Zero Timeout Time, the function selected in 6-01 Live
Zero Timeout Function will be activated.
Function:
Select the time-out function. The function set in
6-01 Live Zero Timeout Function will be activated
if the input signal on terminal 53 or 54 is below
50% of the value in 6-10 Terminal 53 Low Voltage,
6-12 Terminal 53 Low Current, 6-20 Terminal 54
Low Voltage or 6-22 Terminal 54 Low Current for a
time period defined in 6-00 Live Zero Timeout
Time. If several time-outs occur simultaneously,
the frequency converter prioritises the time-out
functions as follows:
1.
6-01 Live Zero Timeout Function
2.
8-04 Control Timeout Function
The output frequency of the frequency
converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent
trip
MG.11.CB.02 - VLT
®
VLT
HVAC Drive Programming Guide
6-01 Live Zero Timeout Function
Option:
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and
trip
Par 6-xx
High Ref./
Feedb. Value'
Par 6-xx
Low Ref./
Feedb. Value'
6-02 Fire Mode Live Zero Timeout Function
Option:
[0]
Off
*
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
3.8.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog
input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
0.07 V
*
®
is a registered Danfoss trademark
Function:
Ref./Feedback
[RPM]
1500
1200
900
600
300
150
1 V
5 V
Par 6-xx
'Low Voltage'or
'Low Current'
Par 6-xx
'High Voltage'or
'High Current'
Function:
The function set in 6-01 Live Zero Timeout
Function will be activated if the input signal
on analogue inputs is below 50% of the value
defined in par. group 6-1* to 6-6* "Terminal
xx Low Current" or "Terminal xx Low Voltage"
for a time period defined in 6-00 Live Zero
Timeout Time.
Function:
[0.00 - par.
Enter the low voltage value. This analog
6-11 V]
input scaling value should correspond to
the low reference/feedback value set in
6-14 Terminal 53 Low Ref./Feedb. Value.
10 V
[V]
Analog input