Parameter Description
3.6.2 4-5* Adj. Warnings
Define adjustable warning limits for current, speed, reference
and feedback.
NOTE
Not visible in display, only in VLT Motion Control Tool, MCT
10.
Warnings are shown on display, programmed output or
serial bus.
I
motor
I
LIM
(P 4-18)
I
HIGH
(P 4-51)
IN RANGE
I
LOW
(P 4-50)
n
n
MIN
LOW
(P 4-11)
(P 4-52)
4-50 Warning Current Low
Range:
Function:
0.00 A
[0.00 -
Enter the I
*
par. 4-51
falls below this limit (I
A]
CURRENT LOW. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 and on relay output 01 or
02. Refer to the drawing in this section.
4-51 Warning Current High
Range:
Size related
[par. 4-50 - par. 16-37 A]
*
4-52 Warning Speed Low
Range:
0 RPM
[0 - par. 4-53 RPM]
*
4-53 Warning Speed High
Range:
Size related
[par. 4-52 - par. 4-13 RPM]
*
®
VLT
HVAC Drive Programming Guide
ON REF
n
[RPM]
motor
n
n
REF
HIGH
MAX
(P 4-53)
(P 4-13)
value. When the motor current
LOW
), the display reads
LOW
Function:
Function:
Function:
®
MG.11.CB.02 - VLT
is a registered Danfoss trademark
NOTE
Any changes in 4-13 Motor Speed High Limit [RPM] will reset
the value in 4-53 Warning Speed High to the same value as set
in 4-13 Motor Speed High Limit [RPM].
If a different value is needed in 4-53 Warning Speed High, it
must be set after programming of 4-13 Motor Speed High
Limit [RPM]
4-54 Warning Reference Low
Range:
-999999.999
[-999999.999 -
*
par. 4-55 ]
4-55 Warning Reference High
Range:
999999.999
[par. 4-54 -
*
999999.999 ]
4-56 Warning Feedback Low
Range:
-999999.999
[-999999.999 -
ProcessCtrlUnit
par. 4-57
*
ProcessCtrlUnit]
4-57 Warning Feedback High
Range:
999999.999
[par. 4-56 -
ProcessCtrlUnit
999999.999
*
ProcessCtrlUnit]
Function:
Enter the lower reference limit.
When the actual reference falls
below this limit, the display
indicates Ref Low. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 and on relay
output 01 or 02.
Function:
Enter the upper reference limit.
When the actual reference
exceeds this limit, the display
reads Ref High. The signal outputs
can be programmed to produce a
status signal on terminal 27 or 29
and on relay output 01 or 02.
Function:
Enter the lower feedback
limit. When the feedback
falls below this limit, the
display reads Feedb Low.
The signal outputs can be
programmed to produce a
status signal on terminal
27 or 29 and on relay
output 01 or 02.
Function:
Enter the upper feedback
limit. When the feedback
exceeds this limit, the
display reads Feedb High.
The signal outputs can be
programmed to produce a
status signal on terminal
27 or 29 and on relay
output 01 or 02.
55
3
3