Parameter Description
20-02 Feedback 1 Source Unit
Option:
[173] ft WG
[174] in Hg
[180] HP
3
3
NOTE
This parameter is only available when using pressure to
temperature feedback conversion.
If the choice Linear [0] is selected in 20-01 Feedback 1
Conversion, then the setting of any choice in 20-02 Feedback
1 Source Unit does not matter as conversion will be one-to-
one.
20-03 Feedback 2 Source
Option:
[0]
No function
*
[1]
Analog input 53
[2]
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[15]
Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-04 Feedback 2 Conversion
Option:
[0]
Linear
*
[1]
Square root
[2]
Pressure to temperature
[3]
Pressure to flow
[4]
Velocity to flow
20-05 Feedback 2 Source Unit
Option:
Function:
See 20-02 Feedback 1 Source Unit for details.
20-06 Feedback 3 Source
Option:
[0]
No function
*
[1]
Analog input 53
[2]
Analog input 54
124
®
VLT
HVAC Drive Programming Guide
Function:
Function:
See 20-00 Feedback 1 Source for
details.
Function:
See 20-01 Feedback 1 Conversion for
details.
Function:
See 20-00 Feedback 1 Source for
details.
MG.11.CB.02 - VLT
20-06 Feedback 3 Source
Option:
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[15]
Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-07 Feedback 3 Conversion
Option:
[0]
Linear
*
[1]
Square root
[2]
Pressure to temperature
[3]
Pressure to flow
[4]
Velocity to flow
20-08 Feedback 3 Source Unit
Option:
Function:
See 20-02 Feedback 1 Source Unit for details.
20-12 Reference/Feedback Unit
Option:
Function:
See 20-02 Feedback 1 Source Unit for details.
20-13 Minimum Reference/Feedb.
Range:
0.000
[-999999.999 -
ProcessCtrlUnit
par. 20-14
*
ProcessCtrlUnit]
NOTE
If operating with 1-00 Configuration Mode set for Open Loop
[0], 3-02 Minimum Reference must be used.
®
is a registered Danfoss trademark
Function:
Function:
See 20-01 Feedback 1 Conversion for
details.
Function:
Enter the desired minimum
value for the remote
reference when operating
with 1-00 Configuration Mode
set for Closed Loop [3]
operation. Units are set in
20-12 Reference/Feedback
Unit.
Minimum feedback will be
-200% of either the value set
in 20-13 Minimum Reference/
Feedb. or in 20-14 Maximum
Reference/Feedb., which ever
numeric value is the highest.