Parameter Description
3.16.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
[0 -
View the signal states from the active digital inputs.
1023 ]
Example: Input 18 corresponds to bit no. 5, '0' = no
*
signal, '1' = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
0 0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53. Current = 0;
Voltage = 1.
[0] Current
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
16-62 Analog Input 53
Range:
0.000
[-20.000 - 20.000 ]
View the actual value at input 53.
*
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54. Current = 0;
Voltage = 1.
[0] Current
®
VLT
HVAC Drive Programming Guide
DI T -33
DI T -32
DI T -29
DI T -27
DI T -19
DI T -18
DI T -37
DI X30/4
DI X30/3
DI X30/2
DI X46/13
DI X46/11
DI X46/9
DI X46/7
DI X46/5
DI X46/3
DI X46/1
Function:
®
MG.11.CB.02 - VLT
is a registered Danfoss trademark
16-63 Terminal 54 Switch Setting
Option:
Function:
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
16-64 Analog Input 54
Range:
Function:
0.000
[-20.000 - 20.000 ]
View the actual value at input 54.
*
16-65 Analog Output 42 [mA]
Range:
Function:
0.000
[0.000 - 30.000 ] View the actual value at output 42 in
*
mA. The value shown reflects the
selection in 6-50 Terminal 42 Output.
16-66 Digital Output [bin]
Range:
Function:
0
[0 - 15 ]
View the binary value of all digital outputs.
*
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual frequency rate on terminal 29.
*
16-68 Pulse Input #33 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual value of the frequency applied
*
at terminal 33 as an impulse input.
16-69 Pulse Output #27 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of impulses applied to
*
terminal 27 in digital output mode.
16-70 Pulse Output #29 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of pulses to terminal 29 in
*
digital output mode.
3
3
117