Beater Rotation

Beater rotation must be clockwise as viewed
looking into the freezing cylinder.
Note: The following procedures should be performed
by a trained service technician.
To correct the rotation on a three-phase unit,
interchange any two incoming power supply lines at
freezer main terminal block only.
To correct rotation on a single-phase unit, change
the leads inside the beater motor. (Follow the
diagram printed on the motor.)
Electrical connections are made directly to the
terminal block provided in the splice box.

Optional Carts

There are two optional carts available.
1.
C20600-AFB: ADA compliant height cart,
not equipped with a door.
2.
C20600-000: Standard height cart with
reversible front door panel and rear panel.
Note: If the door is required on the rear of the
cart instead of the front, the front door panel
and the rear panel can be reversed. To reverse
these panels, remove the five screws on each
panel. Reverse and reinstall the panels, making
sure all screws are reinstalled.
IMPORTANT! For safety purposes, the
freezer must be bolted to the cart using all 4
bolts. Failure to comply could result in personnel
injury and equipment damage.
Model C723

Refrigerant

In consideration of our environment, Taylor
uses only earth friendly HFC refrigerants. The HFC
refrigerant used in this unit is R404A. This
refrigerant is generally considered non­toxic and
non­flammable, with an Ozone Depleting Potential
(ODP) of zero (0).
However, any gas under pressure is potentially
hazardous and must be handled with caution.
NEVER fill any refrigerant cylinder completely with
liquid. Filling the cylinder to approximately 80% will
allow for normal expansion.
Use only R404A refrigerant that conforms
to the AHRI standard 700 specification. The use of
any other refrigerant may expose users and
operators to unexpected safety hazards.
Refrigerant liquid sprayed onto the skin may
cause serious damage to tissue. Keep eyes and skin
protected. If refrigerant burns should occur, flush
immediately with cold water. If burns are severe,
apply ice packs and contact a physician
immediately.
Taylor reminds technicians to be cautious of
government laws regarding refrigerant recovery,
recycling, and reclaiming systems. If you have any
questions regarding these laws, please contact the
factory Service Department.
WARNING: R404A refrigerant used in
conjunction with polyolester oils is extremely
moisture absorbent. When opening a refrigeration
system, the maximum time the system is open must
not exceed 15 minutes. Cap all open tubing to
prevent humid air or water from being absorbed by
the oil.