Connecting External Wiring; Connecting Electric Wiring - Mitsubishi MELSEC-A A1SD71-S2 User Manual

Positioning module
Table of Contents

Advertisement

5. LOADING AND INSTALLATION
.
- . I
.
W L S E G A
5.2.2
Connecting external wirlng
The AlSD71 has the following connectors:
When connecting an electric wire, disassemble as shown in Fig. 5.1.
The disassembly and assembly procedures are as follows:
1) Loosen the four screws, and remove them.
2) Open the cover from the connector side.
3) Connect the electric wire (refer to Section 5.2.3(1) to (3)).
4)
Put connectors into the cover.
5) Pull open the fixed screws.
6) Put the covers together.
7) Fasten the four screws. Use longer screws for cable clamping.
Always keep track of small screws and nuts when disassembling.
Fig.
5.1
Connector
5.2.3
Connecting electric wiring
Connector pin wiring is shown in Fig. 5.2. Connect in accordance with the I/O
numbers (refer to Section 3.7.2).
(1)
Use 0.3 mm2 or less wires. Thicker wires cannot pass through the cable
(2) Solder the wires to the pins. Remove electric wire insulation carefully. Be
clamps.
careful not to cause a short circuit.
Wires should be threaded through an insulating tube.
(3) Secure the electric wire in the cable clamp of a cover.
When there are several connecting electric wires, wrap them together
with tape.
Soldering
ire
+t
Pin arrangement seen
from the connection side
Connection pins include
A1 to A20 and B1 to
820.
Fig. 5.2 Connection
5 - 4