5 Planning the installation

5.11 What you need

Beside the parts delivered with the inverter (see
addititional parts and tools.
Part
For mounting the inverter
M6 mounting screws
For connecting the inverter to the grid (AC)
AC cable
34
34
"4.1 Scope of delivery", p.
Quantity
Image/Description
12
The mounting plate has to be mounted with 12 M6 screws.
Depending on where you mount the inverter (e. g. on a brick wall,
concrete wall, metal frame etc.) you may need additional mounting
material.
This could be:
Wall plugs, washers, washer springs, nuts etc.
-
Use properly sized wire to connect to the correct poles (see table)
AC connector
Current rating
Min. / Max. cable diameter
Min. / Max. wire size
Recommended torque for terminal
screws
AC plug delivered with the inverter can be used with flexible copper
cable.
When calculating the cross section of the cable, consider:
material used
thermal conditions
cable length
type of installation
AC voltage drop
power losses in cable
Always follow the system installation requirements defined for your
country!
France: Follow the system installation requirements defined by UTE
15-712-1 regarding minimum cable sections and protections against
overheating due to high currents!
Germany: Follow the system installation requirements defined by VDE
0100 712 regarding minimum cable sections and protections against
overheating due to high currents!
For a description how to connect the AC cable to the AC connector
see
"6.4 Connecting to the grid (AC)", p.
10), you may need the following
China Aviation
Optical-Electrical
Technology Co.
PVE5T125KE36
100 A
37 ... 44 mm
25 ... 35 mm
2
3 Nm
40.
Installation and Operation Manual for RPI M50A
Installation and Operation Manual for RPI M50A