Industrial Electronic Devices
Setting new Fade Rate value
This command is used to program the new Fade Rate value in the DALI devices.
REQUEST
S_RAT_id_val
(ASCII format)
Where:
'id' = ID of the DALI node (0 ÷ 63) or group (64 ÷ 79) or broadcast (80).
'val' = value of new Fade Rate value to set (0 ÷ FF, Hex representation)
Note:
Just 'id' and 'val' are variables, the rest of the ASCII string is fixed.
Setting new Fade Time value
This command is used to program the new Fade Time value in the DALI devices.
REQUEST
S_TIM_id_val
(ASCII format)
Where:
'id' = ID of the DALI node (0 ÷ 63) or group (64 ÷ 79) or broadcast (80).
'val' = value of new Fade Time value to set (0 ÷ FF, Hex representation)
Note:
Just 'id' and 'val' are variables, the rest of the ASCII string is fixed.
ADFweb.com Srl – IT31010 – Mareno – Treviso
User Manual DALI / Ethernet
Document code: MN67839_ENG
INFO:
www.adfweb.com
Phone +39.0438.30.91.31
Revision 1.001