Industrial Electronic Devices
Scene Programming
This commands are used to program the scenes inside the DALI nodes. It is necessary to send two consecutive commands for the
programming.
REQUEST 1
REQUEST 2
ADFweb.com Srl – IT31010 – Mareno – Treviso
Byte Number
Description
1
0x00
2
0x10
3
0x00
4
0x00
5
0x00
6
0x02
7
0x04
8
Counter (increased for every command) (Hex)
9
0xD1
10
ADV (Hex)
11
0x00
Byte Number
Description
1
0x00
2
0x10
3
0x00
4
0x00
5
0x00
6
0x02
7
0x04
8
Counter (increased for every command) (Hex)
9
DALI ID + 0x80 (Hex)
10
Scene Number + 0x40 (Hex)
11
0x00
User Manual DALI / Ethernet
Document code: MN67839_ENG
INFO:
www.adfweb.com
Phone +39.0438.30.91.31
Revision 1.001