HUAWEI USG6000 Series
Hardware Guide

3.4.1 Mounting a Device to a Specified Location

The USG6306/6308/6330/6350/6360/6370/6380/6390/6390E/
6507/6530/6550/6570/6620/6630 can be mounted in a 19-inch standard cabinet. When no
cabinet is available, you can mount the
USG6306/6308/6330/6350/6360/6370/6380/6390/6390E/6507/6530/6550/6570/6620/6630 on
a workbench.

3.4.1.1 Mounting a Device in a Cabinet

The USG6306/6308/6330/6350/6360/6370/6380/6390/6390E/
6507/6530/6550/6570/6620/6630 can be mounted in a 19-inch standard cabinet through L-
shape guide rails or adjustable guide rails.
Context
The adjustable guide rails (parts 21241561 and 21242247) and L-shaped guide rails are
optional and not delivered with the USG by default. Purchase them as required.
Required instruments:
l
l
Before installing the USG, check the following items:
l
l
l
l
l
You can place either end of the USG chassis towards the cabinet door. In this manual, the
front panel of the USG is towards the cabinet door.
Procedure
Step 1 Install mounting ears on the chassis.
Use a Phillips screwdriver to fix the mounting ears to both sides of the chassis with M4
screws, as shown in
Issue 08 (2017-06-30)
Phillips screwdriver
Floating mounting bar
The cabinet is stable.
Adjustable guide rail 21241561 can be flexibly adjusted from 400 mm to 600 mm in
length and adjustable guide rail 21242247 from 370 mm to 585 mm to be installed in a
600 mm to 800 mm deep cabinet. Before installing the adjustable guide rail, adjust the
distance between the front and rear angle gauges (rack mounting rails/vertical columns)
to satisfy the installation requirements.
The position for the USG in the cabinet is well arranged. Ensure that the USG is 1 U of
clearance from any devices above and below and 150 mm of clearance from any devices
on the right or left.
The USG to be installed is staged near the cabinet for convenience.
From the rear perspective of the chassis, the cooling wind of the USG flows in on the left
and front, and is exhausted on the right. When a USG and a device whose cooling wind
flows in on the right and is exhausted on the left are installed in the same cabinet,
adequate space must be reserved between them to avoid thermal cycles.
Figure