4.4 Setting DIL Switches on Analog Modules of ET 200C

Introduction
In the following analog modules, the lower printed-circuit board accommo-
dates the terminal block plus a number of DIL switch blocks:
These DIL switch blocks can be used to set the station number of the
ET 200C module (optional), the measurement type for the input modules, and
the wiring configuration (2-wire or 4-wire) for the output module.
Every analog module has a DIL switch block for setting the station number
(block S1). The other DIL switch blocks are module-specific.
Note
The settings performed electronically with COM ET 200 Windows as
described in the manual ET 200 Distributed I/O System (Order No.
6ES5 998-3ES12) must always match the settings of the internal DIL
switches of the analog modules.
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
ET200C; AI 4/8
12 bit
ET200C; AI 4
12 bit
ET200C; AO 4
12 bit
Mechanical and Electrical Installation
4-43