Siemens SIMATIC ET 200C Manual page 231

Table of Contents

Advertisement

Parameterization
You parameterize the ET 200C; AI 4/8
COM ET 200 Windows parameterization software.
Where to Look
Parameterization of the ET 200C; AI 4/8
Windows is described in detail in the Help system integrated in the
COM ET 200 Windows program.
The manual entitled ET 200 Distributed I/O System
(Order No. 6ES5 998-3ES12) contains detailed descriptions of how to use
COM ET 200 Windows.
All the parameters for the ET 200C; AI 4/8
table below:
Table 12-1 Parameters for ET 200C Analog Input Module; AI 4/8
1
Byte
Bit
Parameter
08
0
Enable diagnostics CH 0/1
1
Enable diagnostics CH 2/3
2
Enable diagnostics CH 4/5
3
Enable diagnostics CH 6/7
09
0
Enable wire-breakage message
CH 0/1
1
Enable wire-breakage message
CH 2/3
2
Enable wire-breakage message
CH 4/5
3
Enable wire-breakage message
CH 6/7
15
6
Enable diagnostics alarm
7
Enable limit value alarm
16
0 ... 1 Integration time CH 0/1
2 ... 3 Integration time CH 2/3
4 ... 5 Integration time CH 4/5
6 ... 7 Integration time CH 6/7
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
12 bit with the aid of the
12 bit with COM ET 200
12 bit are described in the
12 Bit
Explanation
Enable diagnostics messages by
channel groups
channel groups
Enable wire-breakage detect. by
channel groups
Enable diagnostics alarm of
module
Enable limit value alarm of
module
Set integration time by channel
groups
groups
Analog Modules
Range of values
disable
enable
bl
disable
enable
disable
enable
2.5 ms
16.7 ms
16 7 ms
20 ms
20 ms
100 ms
12-5