Digital Modules
11.4 Digital Input/Output Module ET 200C; DI 16/DO 16
(6ES7 143-0BL00-0XB0 and 6ES7 143-0BL10-0XB0)
Technical Specifications
Baud rates
9.6/19.2/93.75/187.5/500/
1500/3000
12000
Mains buffering
typ. 20 ms
(without sensor and load
voltage supply)
Insulation rating
to VDE 0160
Nominal insulation voltage
(L+ against PE)
60 V AC (75 V DC)
Test voltage
500 V DC
Electrical isolation to
500 V
SINEC L2-DP bus
Power loss
typ. 4.1 W
Weight
approx. 3700 g
Dimensions (W H D)
260 167 83
Diagnostic Functions
Voltage monitoring
green LED "RUN"
SINEC L2-DP bus
red LED "BF"
monitoring
Status of inputs or outputs
red LED "DIA" for
diagnosing groups of 4
inputs/outputs
green LED for status of
inputs
Supply Voltage for Outputs, Load Voltage Supply
and Internal Logic
Nominal value (L+)
24 V DC
Permissible range
20.4 ... 30.2 V
(incl. ripple = max. 3.6 V)
35 V
Value at t < 0,5 s
Short-circuit capability
Yes
Current consumption
Logic
typ. 90 mA
Load
typ. 40 mA
Short-circuit current
max. 6.3 A
1
This baud rate is only relevant in conjunction with the
IM 308-C.
2
If a short-circuit occurs in the sensor supply of an input,
the sensor supply for all of the inputs in the group of 4
will be interrupted.
11-16
Inputs
Number of inputs
1
1
/6000
/
Connection
1
kbaud
6ES7 143-0BL00-0XB0
6ES7 143-0BL10-0XB0
Electrical isolation
Supply voltage for sensors
Permissible total current
per channel
Input voltage
Nominal value
for "0" signal
for "1" signal
Input current for "1" signal typ. 4.5 mA at 24 V
Short-circuit current
limitation
Delay of inputs
2
Connection of 2-wire
BERO
Quiescent input
current
Cable length of the inputs
Outputs
Number of outputs
in groups of
Connection with
6ES7 143-0BL00-0XB0
6ES7 143-0BL10-0XB0
DC 24V/2A
16
via 5-pin circular connec-
tor (4-wire connection)
via cable gland and con-
duit thread
(4-wire connection)
No
(L+) – 0.8 V
max. 4 A
max. 250 mA
24 V DC
–30 ... 5 V
13 ... 30 V
2.3 A for each group of 4
typ. 1.8 ms (0
1)
typ. 1 ms (1
0)
Possible
1.5 mA
max. 50 m
16
8
via 5-pin circular
connector
(3-wire connection)
via cable gland and
conduit thread
(3-wire connection)
ET 200C Distributed I/O Station