Siemens SIMATIC ET 200C Manual page 241

Table of Contents

Advertisement

Table of Measured
The table below shows the digitized measured values for the ET 200C;
Values
AI 4/8
Table 12-12 Digitized Measured Values for ET 200C; AI 4/8
Table of Measured
The four tables below show the digitized measured values for thermocouples
Values
of types K, N, J and E.
Table 12-13 Digitized Measured Values for ET 200C; AI 4/8
If wiring is incorrect or an error occurs in the sensor in the negative, the analog input
module reports underrun if F0C5
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
12 Bit for resistance sensors (Pt 100):
Resistance Sensors
Temperature
Decimal
range standard
Pt 100
850 C
1000.1
32767
1000.0
10000
:
:
850.1
8501
850.0
8500
:
:
–200.0
–2000
–200.1
–2001
:
:
–243.0
–2430
– 243.1
–32768
Thermocouple
Temperature
Decimal
range in C
Type K
1623
32767
1622
16220
:
:
1373
13730
1372
13720
:
:
–270
–2700
–271
–2710
H
Analog Modules
12 Bit for Pt 100
Hexadecimal
7FFF
Overflow
H
2710
H
:
Overload range
2135
H
2134
H
:
Nominal range
F830
H
F82F
H
:
Underdrive range
F682
H
8000
Underrun
H
12 Bit for Type K
Hexadecimal
7FFF
Overflow
H
3FSC
H
:
Overload range
35A2
H
3598
H
:
Nominal range
F574
H
F573
Underdrive range
H
is undershot and outputs 8000
.
H
Range
Range
12-15

Hide quick links: