Siemens SIMATIC ET 200C Manual page 235

Table of Contents

Advertisement

Table of Measured
The table below shows the relationship between analog and digitized
Values
measured values for the measuring ranges:
and
Table 12-5 Digitized Measured Values for ET 200C; AI 4/8
500 mV and
Units
Measured value in mV
80
250
80
250
mV
mV
> 2409
94.10
294.07
2408
94.06
293.95
:
:
:
2049
80.04
250.12
2048
80.00
250.0
1024
40.00
125.00
1
0.039
0.12
0
0.00
0.00
–1
–0.039
–0.12
–1024
–40.00 –125.00 –250.00
–2048
–80.00
–250.0
–2049
–80.04 –250.12 –500.24 –1000.48 1 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
:
:
:
–2408
–94.06 –293.95
< –2409 –94.10 –294.07 –588.13 –1176.26 1 0 1 1 0 1 0 0 1 0 1 1 1 0 0 1
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
1000 mV.
1000 mV)
Digitized measured value
500
1000
500
1000
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
mV
mV
588.13
1176.26 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0 1
587.89
1175.78
0 1 0 0 1 0 1 1 0 1 0 0 0 0 0 0
:
:
500.24
1000.48
0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
500.0
1000.0
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
250.00
500.00
0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
0.24
0.48
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0.00
0.00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–0.24
–0.48
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–500.00
1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0
–500.0
–1000.0
1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
:
:
587.89
–1175.78 1 0 1 1 0 1 0 0 1 1 0 0 0 0 0 0
Analog Modules
80 mV,
250 mV,
12 Bit (Measuring Ranges:
80 mV,
X F O
:
:
500 mV
250 mV,
Range
Overflow
Overload
Overload
range
range
Nominal
range
range
Overload
Overload
range
range
Overflow
12-9