Mechanical and Electrical Installation
4.4.2
Setting the Measurement Type for Analog Module ET 200C;
AI 4/8

12 Bit

Basic Requirement
The lower printed-circuit board in the analog module ET 200C;
AI 4/8
blocks:
Table 4-19 Module-Specific DIL Switch Blocks in ET 200C; AI 4/8
Rules
The rules for setting the measurement type for the analog module ET 200C;
AI 4/8
4-46
12 Bit accommodates the following module-specific DIL switch
DIL switch block
S2
Select 2-wire or 4-wire con-
nection for Pt 100 resistance
S3
Select external/internal and
floating/non-floating com-
pensation for thermocouples
S4
Select floating or non-floa-
ting measurement
12 Bit by means of the DIL switches are as follows:
High-precision measurement with Pt 100 resistance thermometers is
ensured only if you use 4-wire connection.
The usual setting for thermocouple measurements is internal with
non-floating compensation. Use external compensation only if the
reference point has to be outside the analog module ET 200C;
AI 4/8
12 Bit. Spurious voltages can occur, caused for example by
crosstalk at the compensator input.
Non-floating compensation prevents voltage shift in the event of a
common-mode disruption at the compensator.
You should always use non-floating measurement by preference, as this
will suppress the effect of severe common-mode disruptions, for example.
When you close the module, make sure that the cover is correctly seated
as damage may occur if the cover is not aligned with the casing.
Function
Default setting
(as delivered)
OFF
4-wire connection for
thermometers
Pt 100
ON
internal and non-floa-
ting compensation for
thermocouples
OFF
floating measurement
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
12 Bit