Siemens SIMATIC ET 200C Manual page 213

Table of Contents

Advertisement

11.3 Digital Output Module ET 200C; DO 8
(6ES7 142-0BF10-0XB0)
Technical Specifications
Baud rates
9.6/19.2/93.75/187.5/500/
1500/3000
12000
Mains buffering
typ. 20 ms
(without sensor and load
voltage supply)
Insulation rating
to VDE 0160
Nominal insulation voltage
(L+ against PE)
60 V AC (75 V DC)
Test voltage
500 V DC
Electrical isolation to
500 V
SINEC L2-DP bus
Power loss
typ. 4.1 W
Weight
approx. 1000 g
Dimensions (W H D)
223 100 57
Diagnostic Functions
Voltage monitoring
green LED "RUN"
SINEC L2-DP bus
red LED "BF"
monitoring
Group diagnostics for
red LED "DIA"
short-circuit/overload or
wire break
Status of outputs
red LED for individual
diagnostics (short-circuit
or wire break of outputs)
green LED for status of
outputs
Supply voltage for outputs green LED "U
voltage supply of the
outputs
Supply Voltage for Outputs, Load Voltage Supply
and Internal Logic
Nominal value (L+)
24 V DC
Permissible range
20 ... 30 V
(incl. ripple = max. 3.6 V)
35 V
Value at t < 0.5 s
Short-circuit capability
Yes
Current consumption
Logic
typ. 90 mA
Load
typ. 80 mA
Short-circuit current
max. 4 A
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
Outputs
Number of outputs
1
1
/6000
/
Connection
1
kBaud
Electrical isolation
between internal logic and
outputs
Load voltage supply
Nominal value (L1)
Permissible range
(incl. ripple =
max. 3.6 V)
Output current for "1"
signal
Nominal value
Permissible range
Lamp load
Permissible total current
Ambient temperature:
– 25 ... +25 C
+26 ... +40 C
+41 ... +60 C
Residual current for "0"
signal
2
Wire-break recognition
No wire-break recognition
Short-circuit diagnostics
" for load
L
signal
Switching frequency
at resistive load
at inductive load
Limitation of voltage
induced on circuit
interruption
Cable length of outputs
1
This baud rate is only relevant in conjunction with the
IM 308-C.
2
The diagnostics signal remains for a further 20 s
(approx.) after a short-circuit has been eliminated (e.g.
when an output is reset).
Digital Modules
DC 24V/2A
8
via 5-pin circular
connector
3-wire connection per
channel
Yes, 500 V
24 V DC
20 ... 30 V
2 A per channel
10 mA ... 2 A per channel
max. 5 W
max. 10 A
max. 8 A
max. 4 A
max. 0.5 mA
typ. I
1 mA
typ. I
20 mA
typ. 3.5 A
100 Hz
0.5 Hz
typ. (L+) – 50 V
max. 30 m
11-11