All about VLT 2800
Safeguards
Electronic thermal motor protection against overload.
Temperature monitoring of the power module ensures that the frequency converter cuts out if the temperature
reaches 100 °C. An overload temperature cannot be reset until the temperature of the power module is below
70 °C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter cuts out.
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate
circuit voltage is too low or too high.
The frequency converter is protected against ground fault on motor terminals U, V, W.