4.7.5 Process Words

The block of process words is divided into 2 blocks of 16
bits, which always occur in the defined sequence.
Illustration 4.28 Block of Process Words
Control telegram
(master⇒slave)
Control telegram
(slave⇒master)
Table 4.10 Function of PCD 1 and PCD 2
4.7.6 Control Word According to FC
Protocol
To select FC protocol in the control word, set parameter
512 Telegram Profile to [1] FC protocol.
The control word is used to send commands from a master
(e.g. a PC) to a slave (frequency converter).
Illustration 4.29 Control Word According to FC Protocol
110
Conversion
factor
73
2
100
1
0
-1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
PCD 1
Control word
Reference-value
Status word
Present output
Danfoss A/S © Rev. May/2014 All rights reserved.
Design Guide
Bit
00
0.1
01
02
10
03
1
04
0.1
05
06
07
08
09
10
11
12
13
14
15
Table 4.11 Bit Definition
Bit 00/01
Bit 00/01 is used to select between the 4 pre-programmed
references (parameters 215-218 Preset reference) according
PCD 2
to Table 4.12.
Preset ref.
1
frequency
2
3
4
Table 4.12 Bit 00/01
NOTICE
In parameter 508 Selection of preset reference, a selection
is made to define how bit 00/01 gates with the
corresponding function on the digital inputs.
Bit 02, DC brake
Bit 02='0' causes DC braking and stop. Brake voltage and
duration are preset in parameters 132 DC brake voltage and
126 DC braking time.
NOTICE
In parameter 504 DC brake, a selection is made to define
how bit 02 gates with the corresponding function on a
digital inpu
Bit 03, Coasting stop
Bit 03='0' causes the frequency converter to immediately
release the motor (the output transistors are shut off), so
that it coasts to a standstill.
Bit 03='1' causes the frequency converter to be able start
the motor if the other starting conditions have been
fulfilled.
Bit=0
Preset ref. lsb
Preset ref. msb
DC braking
Coasting stop
Quick stop
Freeze outp. freq.
Ramp stop
Ramp 1
Data not valid
No function
Relay 01 activated
No function
Digital output Terminal 46
Select Setup, lsb
Select Setup, msb
Parameter
215
216
217
218
Bit=1
Start
Reset
Jog
Ramp 2
Data valid
activated
Reversing
Bit 01
Bit 00
0
0
0
1
1
0
1
1
MG27E402