Input Board 4 (Ib4) - Samson Trovis 6400 Mounting And Operating Instructions

Automation system, process control stations
Table of Contents

Advertisement

Soldering jumpers
4.1.4. Input board 4 (IB 4)
Input board 4 is no longer available.
Note: Select the desired input signal and close the related soldering jumpers listed in line 3 or the following
ones of the table below (depending on type of signal selected)! Open all remaining jumpers associated with
the corresponding input (line 2). See Fig. 5 for the location of the input board. The soldering jumpers
associated with the binary inputs are described in section 4.1.1., page 14.
Input signal
Current
Voltage
−100 to 100 mV 14
Potentiometer
Transmitter supply
Thermocouples
Type U
Type R
1000 to 1700 °C 15
Type T
Input 1
(Ai 1)
Jumpers:
10 to 19
0 to 20 mA
4 to 20 mA
−20 to 20 mA
0 to 1 V
0 to 5 V
0 to 10 V
0.2 to 1 V
1 to 5 V
2 to 10 V
0 to 50 mV 17
0 to 100 mV 16
−50 to 50 mV 15
0 to 1kΩ −
0 to 200 °C 17
150 to 400 °C 16
300 to 600 °C 15
0 to 600 °C 14
0 to 700 °C 17
500 to 1200 °C 16
0 to 1700 °C 14
0 to 150 °C 17
100 to 250 °C 16
200 to 400 °C 15
0 to 400 °C 14
Determining the input signals
Input 2
Input 3/4
(Ai 2)
(Ai 3/4)
Jumpers:
Jumpers:
20 to 26
41 to 47
21
41, 45
21, 24
41, 44, 45
21, 25, 26
21
41
22
42
23
43
21, 24
41, 44
22, 24
42, 44
23, 24
43, 44
42, 46, 47
40, 41, 44, 45, 49
20, 21, 24, 29
17