Establishing Connection With The Control Station - Samson TROVIS 5724-8 Mounting And Operating Instructions

Without/with fail-safe action electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

Installation
5.7.1

Establishing connection with the control station

Î Connect the bus connection line for communication over Modbus RTU protocol.
Fig. 5-6: Bus connection line with three-pin round connector
Note
Fit the first and last bus participant of the RS-485 bus with an external bus termination.
5-8
White
A (incoming)
Brown
B (incoming)
Green
A' (outgoing)
Yellow
B' (outgoing)
Black
Shielding
EB 5724-8 EN