Operation
Calibrating the span for the outputs Y1, Y2 and Ao1
When calibrating the span for the outputs Y1, Y2 and Ao1, proceed as follows:
Connect a highly-accurate meter to the output to be calibrated.
First, follow steps 1. to 6. listed under "Calibrating the input characteristic via 5 coordinates"
(see above).
7.
Select desired output Y1, Y2 or Ao1 by pressing the C key. A scale from 0 to 100 % comes
up at the bottom of the display.
8.
Use the G and H keys to adjust the desired end value of the output signal range. Check
this value with the highly-accurate meter. When the output signal is within the calibration
range, CAL and the selected output alternate in the lower line of the display.
9.
Press A key to accept the calibrated end value.
10. Repeat steps 7 to 9 to calibrate the other outputs or exit the Ai level by pressing the F key.

6.8.Fir level (displaying the firmware number)

This level is used to view the version number of the EPROM used in the process control station,
as well as the current RS-485 interface version. Should you have any inquiry about the device,
always specify the version number of your process control station because the software might
have been modified for the following versions.
Proceed as follows:
The process control station is in the OPERATING level.
1.
Press A key. I-O appears on the display.
2.
Press D key until "Fir" comes up on the display.
3.
Press A key. C (for controller = process control station) appears in the lower line of the
display, and the valid version number is indicated in the upper line of the display.
Press C key. Si (for serial interface) appears in the lower line of the display, and the valid
version number is indicated in the upper line of the display. If 0.0 appears here, this means
that no interface board is installed.
5.
Press F key to exit the Fir level.

6.9.CHE level (checking the display panel)

This level is used to check proper functioning of all the display elements shown on the last page
of this manual.
Proceed as follows:
The process control station is in the OPERATING level.
1.
Press A key. I-O appears on the display.
2.
Press D key until CHE comes up on the display.
3.
Press A key. All display elements are indicated on the display, as shown on the last page
of this manual.
4.
Press F key to exit the CHE level.
Fir level (displaying the firmware number)