Function Code 02 (Read Input Status); Function Code 05 (Force Single Coil); Function Code 03 (Read Holding Register) - Samson Trovis 6400 Mounting And Operating Instructions

Automation system, process control stations
Table of Contents

Advertisement

Interface RS-485

9.5.2. Function code 02 (Read Input Status)

This function code allows to read the current status of the binary inputs bi 1, bi 2 and bi 3
directly at the input of the slave, no matter whether the respective binary input was configured
in the process control station.
For the query from the central control station and the response from the process control station,
see Read Coil Status (Function code 01).

9.5.3. Function code 05 (Force Single Coil)

The central control station can modify a logic condition in the process control station.
Example: Write coil 09 (MANUAL/AUTOMATIC changeover).
coil 09 must set to "0" in order to place the process control station in the AUTOMATIC mode.
In this example, the address of the process control station is 12.
Query from the control station
Address
Function
0C
05
Response from the process control station
Address
Function
0C
05
The fourth byte contains number 9 (hexadecimal). If a coil is set to "1", byte 5 must transmit the
information FF. If it is to be deleted, 00 has to be transmitted.

9.5.4. Function code 03 (Read Holding Register)

Analog variables can be read from the process control station and, after conversion to the
numeric format, displayed on the PC (controlled variable, set point (reference variable) etc.),.
Example: Read holding register no. 1
This register contains the device identification. The address of the process control station is 1.
Query from the control station
Address
Function
01
03
Response from process control station
Address
Function
01
03
Since, in this example, only register 1 is read and this register always contains the decimal
value 6412, it can be used to check the device identification.
Coil
high
low
00
09
Coil
high
low
00
09
Holding register no.
high
low
00
00
Quantity of
Value of register 1
bytes
high
02
19
Functions supported by the Modbus protocol
Coil
on
off
FF
00
Coil
on/off
FF
00
Quant. of holding registers
high
low
00
01
low
0C
Checksum
low
high
5D
25
Checksum
low
high
5D
25
Checksum
low
high
84
0A
Checksum
low
high
B3
D1
63