Operation
Opening the ADAPTATION level and accessing the adaptation steps
The process control station is in the OPERATING level. All settings required for adaptation have
been made (1. and 2.).
1.
Press A key.
2.
Press C key twice. AdP appears on the display.
3.
Press A key. AdP and oFF appear on the display.
4.
Press A key. oFF changes to on which flashes on the display.
5.
Press A key. The display no longer flashes.
6.
Use C and D keys to change over between the following adaptation steps:
AdP and flashing PA (adaptation parameters can be set)
AdP and flashing Aut (controller conducts adaptation automatically)
AdP and flashing nb (noise measurement can be initiated manually)
AdP and flashing idF (identification can be initiated manually; not possible until after noise
measurement)
AdP and flashing Scd and AdP (calculation of section factors can be manually initiated for
scheduling; not possible until after noise measurement and identification)
AdP and on (adaptation can be switched on/off)
7.
Selected the desired adaptation step, then press the A key.
The selected adaptation step is executed.
Modifying adaptation parameters
1.
Follow steps 1. to 6. as described above under "Opening the ADAPTATION level and
accessing the adaptation steps". For step 6, select PA AdP .
2.
Press A key. The parameter table and AP or AP 1 appear on the display. AP stands for
the adaptation parameters of the fixed set point, follow up, ratio or synchro controller;
AP1 stands for the parameters of the master controller.
3.
The individual adaptation parameters can be selected and modified in the same way as
the parameters in the PARAMETER level (see p. 32).
Completing or aborting an adaptation step
1.
When defining the adaptation parameters, the parameter table and AP or AP1 appear on
the display. Press F key. Press A key for all other adaptation steps. The process control
station remains in the ADAPTATION level. An other adaptation step can be selected.
Completing or aborting the adaptation
1.
Press F key. The process control station switches to the OPERATING level.
AdP level (adaptation of the control parameters)