AdP level (adaptation of the control parameters)
Display field
t >T s K 3
X >GWX
t >T s K 3
1)
Fig. 35 ⋅ Operational flow chart for identification
50
2)
1)
System with self-regulation
2)
System without self-regu-
lation
Status
Sequence of operations
display
0
Checks starting condition
Checks if system has assumed
a calm state
1
Checks if pulse was imposed
on system
2
Activates control pulse
Waits for system response
3
System response determined
4
Controlled system stationary
First calculation of control
parameter set 1 (basic values)
Inactivates control pulse
for system response
5
Inactivates control pulse for
system response
6
Inactivates control pulse
First calculation of control
parameter sets 1 and 2 (basic
values).
Changes over to selected
operating mode or
calculates correction of
control pulse
Waits for system
to become stationary
7
Activates corrected control
pulse
Waits for system response
8
System response determined
Waits for system to
become stationary
First calculation of control
parameter set 1 (basic values)
9
Inactivates control pulse
Waits for system response
10
System response determined
Waits for system to
become stationary
First calculation of control
parameter set 2 (basic values)
Changes over to selected
operating mode
End
End of identification
IdF