Coil - Status Data Point List for the TROVIS 6412 Industrial Controller
CL No.
Designation of data point
001
Centralized fault
002
Cold restart
003
Data changes
004
Local operation
005
Reserved
006
Reserved
007
Reserved
008
Reserved
Operating modes
009
Manual/Automatic mode
010
Master/follower controller
011
Internal/external set point active
012
External position feedback
013
External system ready
014
Timeout
015
Adaptation on/oFF
016
Adaptation (runs automatically)
Status message
017
Min. limitation of output variable
018
Max. limitation of output variable
1)
Access
Status
0 (= Off)
R
0= None
R
0= None
R/W
0= None
R
0= None
R
0
R
0
R
0
R
0
R/W
0= Automatic mode
R/W
6)
0= Master controller
R/W
6)
0= Internal
R
0
R
0
R/W
0
6)
R/W
6)
0
R/W
0
R
0
R
0
Comments
1 (= On)
1= Active
Active when holding registers 22, 23, 24 <> 0
1= Active
4)
1= Were made
Active when data were changed by the
operator; reset with COIL 65
1= Active
TROVIS 6412 is operated either with the
COPA pen, the TROVIS 6482 program or by
means of the front-panel keys; any displayed
data are not updated
1= Manual mode
2)
1= Follower controller
Cannot be changed when controlled by
1= External
binary input
1
1
4)
1
1
4)
1 = Activated
5)
If active, holding registers 25, 26 show the
current status
1
1