TROVIS 6412 (panel-mounting unit)

5. Electrical connections

When making the electrical connections, note the VDE 0100 regulations and the regulations
valid in the country where the control station is intended to be installed.
Use shielded cables for the signal lines of the analog and binary inputs, which are installed
outside the control cabinets, in order to avoid measuring errors or other interferences. Inside
the control cabinets, these lines have to be installed separately from the control and power
supply lines.
The shieldings of the lines are to be grounded on one side at the neutral point of the measuring
and control system.
5.1. TROVIS 6412 (panel-mounting unit)
The device has plug-in terminals for wires with cross-sections of 0.5 to 1.5 mm
Binary inputs
Switching contact
81 82 83 84 85 86
bi 1
bi 2
bi 3
Continuous control outputs
31 32 33
0
1)
Y1 Y2
Binary outputs
87 88 89 90 91 92
+
1)
1)
bo 1
bo 2
bo 3
Power supply
N
L
Fig. 7 ⋅ Terminal assignment of TROVIS 6412
22
External switching voltage
81 82 83 84 85 86
+
bi 1
Switching output
47 48 49
L1
N
Limit relay
41 42 43 51 52 53
G1
Serial interface RS-485
96 97 98 99
T(A)
T(B)
+
+
bi 2
bi 3
Analog output
+
1)
G2
2)
For 2-wire bus
R(B)
Terminals 96 and 97
R(A)
Electrical connections
2
(DIN 45 140).
1)
34 35
+
Ao 1
1)
2)
,
Optional equipment