Grid Monitoring And Grid Limits - SMA MEDIUM VOLTAGE POWER STATION 500SC-JP System Manual

Hide thumbs Also See for MEDIUM VOLTAGE POWER STATION 500SC-JP:
Table of Contents

Advertisement

SMA Solar Technology AG
Name
Description
PF-PFEx-
Substitute value of the ex-
tSubValR
citation type in normal
feed-in operation during
communication distur-
bance
PwrMonEr-
Mode used in the event
rMod
of communication distur-
bance
PwrMonErrTm
Communication down-
time until substitute val-
ues are used
QoDEna
Activates/deactivates the
function "Q at Night"
QoDDccOffDe-
Delay time until the DC
lay*
switchgear opens in the
operating state
"Q at Night"
* You can only view this parameter.
** To change this parameter, you must enter the installer password.
*** To view or change this parameter, you must enter the installer password.

14.2.1.2 Grid Monitoring and Grid Limits

To change these parameters, you must enter the installer password.
Name
Description
VRtg
Nominal line-to-line volt-
age of the utility grid
VCtlMax
Threshold for overvolt-
age release level 3
VCtlMaxTm
Delay time for overvolt-
age level 3
VCtlhhLim
Threshold for overvolt-
age release level 2
VCtlhhLimTm
Delay time for overvolt-
age level 2
VCtlhLim
Threshold for overvolt-
age release level 1
VCtlhLimTm
Delay time for overvolt-
age level 1
VCtllLim
Threshold for undervolt-
age release level 1
System Manual
Value/range
Explanation
OvExt
Overexcited
UnExt
Underexcited
LastVal
Use of last default values re-
ceived
SubVal
Use of substitute values
1 s to 999 s
Off
Deactivated
On
Activated
0 s to 86,400 s
Range
Explanation
1 V to 70,000 V
100% to 150%
0 ms -
to 1,000,000 ms
100% to 150%
0 ms -
to 1,000,000 ms
100% to 150%
0 ms -
to 1,000,000 ms
0% to 100%
14 Operating Data and Parameters
Default
value
OvExt
LastVal
300 s
Off
3,600 s
Default value
20,000 V
0
1,000,000 ms
130%
100 ms
110%
500 ms
80%
MVPS22JP-SH-en-11
229