SMA Solar Technology AG
Name
Description
WGraEna**
Activation of the active
power change gradient
WGraRe-
Activation of the decou-
conEna**
pling protection ramp for
reconnection
P-VtgGraNom
Active power gradient
**
for voltage-dependent
active power limitation
P-VtgEna
Activation of voltage-de-
pendent active power
limitation
P-VtgNomP1
Voltage at point 1
P-VtgNomP2
Voltage at point 2
P-VtgAtMin
Minimum active power
with voltage-dependent
active power limitation
PwrApLimitPrio
Prioritization of reactive
***
power or active power
SDLimComSrc
Selection of the SDLimit
***
source
P-WSubVal
Substitute value for ac-
tive power limitation out-
side of normal feed-in
operation during commu-
nication disturbance
Q-VArSubVal
Substitute value for reac-
tive power setpoint out-
side of normal feed-in
operation during commu-
nication disturbance
PF-PFSubVal
Substitute value for cos φ
outside of normal feed-in
operation during commu-
nication disturbance
PF-PFExtSubVal Substitute value for exci-
tation type during com-
munication disturbance
System Manual
Value/range
Explanation
Off
Deactivated
On
Activated
Off
Deactivated
On
Activated
0.017%/s to
100.000%/s
Off
Deactivated
On
Activated
100% to 120%
90% to 120%
0% to 100%
PrioPwrRtPrioPwrRt
Prioritization of reactive power
PrioPwrAt
Prioritization of active power
CAN
Interface of the communication
unit
UART
Via SMA Net
0 kW to 1,000 kW
Sunny Central 500CP-JP
Sunny Central 630CP-JP
Sunny Central 800CP-JP
−220 kVAr to
Sunny Central 500CP-JP
+220 kVAr
−310 kVAr to
Sunny Central 630CP-JP
+310 kVAr
−385 kVAr to
Sunny Central 800CP-JP
+385 kVAr
0.5 to 1
The value 0.5 cannot be reached
in normal operation.
OvExt
Overexcited
UnExt
Underexcited
14 Operating Data and Parameters
Default
value
On
Off
0.166%/s
Off
111%
110%
20%
PrioPwrRtPri-
oPwrRt
UART
500 kW
700 kW
880 kW
0 kVAr
1
OvExt
MVPS22JP-SH-en-11