SMA MEDIUM VOLTAGE POWER STATION 500SC-JP System Manual page 226

Hide thumbs Also See for MEDIUM VOLTAGE POWER STATION 500SC-JP:
Table of Contents

Advertisement

14 Operating Data and Parameters
Name
Description
PF-WLockTm
Waiting time for activa-
tion or deactivation of
the cos φ(P) characteris-
tic curve
Q-VDif**
Definition of voltage
change leading to a
change in reactive
power
Q-VArGra**
Definition of the reactive
power setpoint change in
one voltage step
Q-VDifTm**
Time period for which a
voltage change must be
present before the reac-
tive power setpoint Q-
VArGra changes.
Q-VRtgOfsNom
Change the nominal volt-
**
age VRtg of the voltage-
dependent reactive
power control.
Q-VArGraNom
Reactive power gradient
**
Q-VolWidNom
Voltage range
**
Q-VolNomP1
Voltage at point 1
**
Q-VolNomP2
Voltage at point 2
**
Q-VArTmsSpnt
Time setting of the char-
**
acteristic curve point
Q-VArTmsVtg
Connection delay of the
**
grid voltage
Q-EnaTmsVtg
Activation of the connec-
**
tion delay of the grid
voltage in parameter Q-
VArTmsVtg
WGra**
Gradient of active power
change
226
MVPS22JP-SH-en-11
Value/range
Explanation
0 s to 100 s
0.1% to 10%
The value refers to the nominal
voltage VRtg.
0% to 100%
The value refers to the nominal
power Pmax.
0 s to 120 s
−10% to +10%
This parameter is only active if
the parameter Q‑VArMod is set
to VArCtlCol.
0%/V to 22.0%/V
Sunny Central 500CP-JP
0%/V to 15.7%/V
Sunny Central 630CP-JP
0%/V to 12.5%/V
Sunny Central 800CP-JP
0% to 20%
80% to 120%
80% to 120%
0.2 s to 20 s
0.2 s to 20 s
Off
Deactivated
On
Activated
1%/s to 100%/s
SMA Solar Technology AG
Default
value
2 s
1%
1%
1 s
0%
0%/V
0%
100%
100%
10 s
10 s
Off
100%/s
System Manual