14 Operating Data and Parameters
Name
Description
PVStrT
Once the specified time
has elapsed, the inverter
switches from the operat-
ing state "Grid monitor-
ing" to the operating
state "Grid monitoring
time reached".
VArGra**
Gradient of reactive
power change
QoDInvCurPv
Minimum allowed re-
***
verse current to PV array
MppFact
Ratio between maximum
power P
at the maximum power
point and the product of
open-circuit voltage V
and short-circuit current I
SC
Serial Number
Inverter serial number
***
CntrySet*
Selection of valid power
frequency
Parameter can only be
changed in the operating
state "Stop".
CardFunc*
MMC/SD memory card
function
DtSet
Date:
TmSet
Time
TmZn
Time zone
ExtSolIrrOfs
Offset of the external ir-
radiation sensor
ExtSolIrrGain
Amplification of external
irradiation sensor
234
MVPS22JP-SH-en-11
Value/range
1 s to 300 s
0%/s to 200%/s
−1,600 A to 0 A
0.5 to 1
of the PV cell
MPP
OC
0 to 2147483647
J50
J60
ForcedWrite
StoFailStt
20060101 to
20991231
0 to 235959
GMT ‒12:00 to
GMT 12:00
−5,000 to 5,000
−1,000 to 1,000
SMA Solar Technology AG
Explanation
For 50 Hz grid
For 60 Hz grid
Eject SD memory card
Write fault memory to SD mem-
ory card
yyyymmdd
hhmmss
Configurable time zones
Default
value
90 s
20%/s
−60 A
0.8
0
0
0
0
GMT 9:00
0
1
System Manual