9 Troubleshooting
Error no. Explanation
7600
Communication between touch dis-
play and communication unit is in-
terrupted. The error number ap-
pears on the display only.
7601
Internal inverter error
7602
Internal communication error has
occurred or communication is inter-
7605
rupted.
7704
Faulty switching status of the DC
switchgear
7706
The AC disconnection unit is open
or was tripped.
7707
Faulty switching state of the AC
contactor
7708
Faulty switching status of Re-
mote GFDI
7709
90% of switch cycles of the DC
switchgear reached.
7710
100% of switch cycles of the DC
switchgear reached.
7714
Maximum number of GFDI switch
cycles reached.
7801
The surge arrester is defective or
the back-up fuse of the surge ar-
rester was tripped.
7901
Reverse current has occurred in PV
array.
8004
The inverter starts to derate due to
overcurrent at the DC switchgear
(SMID).
8701
External active power setpoints
are smaller than 2 mA and there-
fore invalid. The last valid value or,
after a day change, Pmax is
used. Once valid setpoints are
available again, these will be
used.
130
MVPS22JP-SH-en-11
Inverter behavior
Corrective measures
S1
S2
R
W
W
• Check cabling between touch display
• Contact Service partner.
30 s
1 min x
• Contact Service partner.
30 s
1 min x
• Contact Service partner.
30 s
1 min x
• Contact Service partner.
30 s
Q
• When disconnecting the inverter, check
• Contact Service partner.
30 s
Q
• Contact Service partner.
30 s
Q
• Contact Service partner.
W
W
• Contact Service partner.
10 s
10 s
• Contact Service partner.
30 s
30 s
• Contact Service partner.
30 s
30 s
• Replace GFDI.
W
W
• Check the surge arrester.
• Check the back-up fuse of the surge
1 min D
x
• Contact Service partner.
W
W
W
W
• Contact Service partner.
SMA Solar Technology AG
and communication unit.
that all motor-driven circuit breaker
switches are set to the OFF position. If
not, set all switches to OFF.
arrester.