SMA MEDIUM VOLTAGE POWER STATION 500SC-JP System Manual page 123

Hide thumbs Also See for MEDIUM VOLTAGE POWER STATION 500SC-JP:
Table of Contents

Advertisement

SMA Solar Technology AG
Error no. Explanation
0404*
Frequency change per second too
high for grid operation
0502*
Power frequency is too low. Power
frequency disturbance detected by
standard monitoring.
0503*
Power frequency is too high.
Power frequency disturbance de-
tected by standard monitoring.
0504*
Power frequency is too low. Power
frequency disturbance detected by
redundant monitoring.
0505*
Power frequency is too high.
Power frequency disturbance de-
tected by redundant monitoring.
0506*
The inverter has detected a stand-
alone grid and has disconnected
from the utility grid.
0801*
One line conductor of the utility
grid has failed.
0802*
1301
Left-hand rotating magnetic field is
connected.
1500
The conditions for grid reconnec-
tion have not yet been reached af-
ter a grid error.
* Depending on the parameterization, the disturbance message may have to be acknowledged manually.
System Manual
Inverter behavior
Corrective measures
S1
S2
R
30 s
30 s
30 s
30 s
• Check power frequency.
• Check the display of the grid monitoring
• Make sure the fuses in the load circuit
30 s
30 s
30 s
30 s
30 s
30 s
W
W
• Check power frequency.
30 s
30 s
• Check the grid voltage.
• Make sure the external fuses work
• Make sure the AC cable connections
30 s
Q
• Check phase position.
• Make sure all fuses are switched on.
W
W
• Check the power frequency and grid
9 Troubleshooting
relay.
function properly.
properly.
are tight.
voltage.
MVPS22JP-SH-en-11
123