6 Commissioning
Procedure:
1. Set the protective device (see document "MVSG - Protection Relay Settings" and documentation of the medium-
voltage switchgear). Observe the maximum current values on the medium-voltage side.
Medium-voltage
switchgear
Manufacturer of the
medium-voltage
switchgear: Schneider
Electric
Type of the medium-volt-
age switchgear: FBX
Protective device:
Woodward WIC1-2PE
Manufacturer of the
medium-voltage
switchgear: Schneider
Electric
Type of the medium-volt-
age switchgear:
FLUSARC
Protective device: VIP
45
Medium-voltage
switchgear
Manufacturer of the
medium-voltage
switchgear: Schneider
Electric
Type of the medium-volt-
age switchgear: FBX
Protective device:
Woodward WIC1-2PE
80
MVPS22JP-SH-en-11
Grid voltage
Current on the high-voltage side of the MV transformer in-
[kV]
cluding 10% overload [A]
500 kVA
10
31.75
11
28.87
12
26.46
13.2
24.06
13.8
23.01
15
21.17
20
15.88
22
14.43
23
13.81
24.94
12.73
30
10.58
31.5
10.08
33
9.62
Grid voltage
Current on the high-voltage side of the MV transformer in-
[kV]
cluding 10% overload [A]
1000 kVA
10
63.51
11
57.74
12
52.92
13.2
48.11
13.8
46.02
15
42.34
20
31.75
22
28.87
23
27.61
SMA Solar Technology AG
630 kVA
800 kVA
40.01
50.81
36.37
46.19
33.34
42.34
30.31
38.49
28.99
36.82
26.67
33.87
20.01
25.40
18.19
23.09
17.40
22.09
16.04
20.37
13.34
16.94
12.70
16.13
12.12
15.40
1260 kVA
1600 kVA
80.02
101.61
72.75
92.38
66.68
84.68
60.62
76.98
57.99
73.63
53.35
67.74
40.01
50.81
36.37
46.19
34.79
44.18
System Manual