14 Operating Data and Parameters
Name
Description
QoDQ-
Reactive power setpoint
VArMod**
in the operating mode
"Q at Night"
Q-VAr
Reactive power in kVAr
QoDQ-Var**
Reactive power setpoint
in the operating mode
"Q at Night"
Q-VArNom
Reactive power in %
QoDQ-
Reactive power in % in
VArNom
the operating state
"Q at Night"
224
MVPS22JP-SH-en-11
Value/range
Explanation
Off
Sets reactive power to 0 kVAr
and displacement power factor
cos φ to 1
VArCtlCom
Specifies reactive power via ex-
ternal control unit, such as the
Power Reducer Box
VArCnst
Specifies reactive power in kVAr
via the parameter QoDQ-VAr
VArCnstNom
Specifies reactive power in % via
the parameter QoDQ-VArNom
VArCnstNomAnIn
The reactive power setpoint is im-
ported via an analog input.
VArCtlVol
Specifies reactive power as a
function of the grid voltage
VArCtlVolHystDb
Specifies reactive power as a
function of the grid voltage (Q =
f(V) characteristic curve)
VArCtlVolHysDbA
Specifies reactive power as a
function of the grid voltage with
activation power
−220 kVAr to
Sunny Central 500CP-JP
+220 kVAr
−310 kVAr to
Sunny Central 630CP-JP
+310 kVAr
−385 kVAr to
Sunny Central 800CP-JP
+385 kVAr
−500 kVAr to
Sunny Central 500CP-JP
+500 kVAr
−700 kVAr to
Sunny Central 630CP-JP
+700 kVAr
−880 kVAr to
Sunny Central 800CP-JP
+880 kVAr
−100% to 100%
−100% to +100%
SMA Solar Technology AG
Default
value
Off
0 kVAr
0 kVAr
0%
0%
System Manual