SMA MEDIUM VOLTAGE POWER STATION 500SC-JP System Manual page 228

Hide thumbs Also See for MEDIUM VOLTAGE POWER STATION 500SC-JP:
Table of Contents

Advertisement

14 Operating Data and Parameters
Name
Description
P-WSubValRun
Substitute value for ac-
tive power limitation in
normal feed-in operation
during communication
disturbance
Q-VLockInW** Voltage value from
which the Q(V) charac-
teristic curve is activated,
in % relative to the nomi-
nal voltage
Q-VLockOutW
Voltage value from
**
which the Q(V) charac-
teristic curve is deacti-
vated, in % based on the
nominal voltage
Q-VLockInTm
Waiting time for activa-
**
tion of the Q(V) charac-
teristic curve
Q-VLockOutTm
Waiting time for deacti-
**
vation of the Q(V) char-
acteristic curve
Q-
Reactive power gradient
VArGraNomPo
at a positive change of
s**
nominal voltage
Q-
Reactive power gradient
VArGraNomN
at a negative change of
eg**
nominal voltage
Q-
Substitute value for reac-
VArSubValRun
tive power setpoint in
normal feed-in operation
during communication
disturbance
PF-
Substitute value cos φ in
PFSubValRun
normal feed-in operation
during communication
disturbance
228
MVPS22JP-SH-en-11
Value/range
Explanation
0 kW to 1,000 kW
Sunny Central 500CP-JP
Sunny Central 630CP-JP
Sunny Central 800CP-JP
0% to 100%
0% to 100%
0 s to 100 s
0 s to 100 s
0%/V to 44.06%/V
Sunny Central 500CP-JP
0%/V to 31.47%/V
Sunny Central 630CP-JP
0%/V to 25.04%/V
Sunny Central 800CP-JP
0%/V to 44.06%/V
Sunny Central 500CP-JP
0%/V to 31.47%/V
Sunny Central 630CP-JP
0%/V to 25.04%/V
Sunny Central 800CP-JP
−220 kVAr to
Sunny Central 500CP-JP
+220 kVAr
−310 kVAr to
Sunny Central 630CP-JP
+310 kVAr
−385 kVAr to
Sunny Central 800CP-JP
+385 kVAr
0.5 to 1
The parameter should not fall be-
low 0.8 in normal operation.
SMA Solar Technology AG
Default
value
500 kW
700 kW
880 kW
0%
0%
2 s
2 s
0%/V
0%/V
0 kVAr
1
System Manual