SMA MEDIUM VOLTAGE POWER STATION 500SC-JP System Manual page 222

Hide thumbs Also See for MEDIUM VOLTAGE POWER STATION 500SC-JP:
Table of Contents

Advertisement

14 Operating Data and Parameters
Name
Description
Qmax**
Limitation of reactive
power
QEnsure**
Guaranteed reactive
power
QoDQmax*
Limitation of reactive
power in the operating
state "Q at Night".
The reactive power can-
not exceed Qlimit.
PFAbsMin*
Limitation of the displace-
ment power factor cos φ
222
MVPS22JP-SH-en-11
Value/range
Explanation
0 kVAr to 220 kVAr
Sunny Central 500CP-JP
0 kVAr to 310 kVAr
Sunny Central 630CP-JP
0 kVAr to 385 kVAr
Sunny Central 800CP-JP
0 kVAr to 500 kVAr
Sunny Central 500CP-JP
0 kVAr to 700 kVAr
Sunny Central 630CP-JP
0 kVAr to 880 kVAr
Sunny Central 800CP-JP
0 kVAr to 500 kVAr
Sunny Central 500CP-JP
0 kVAr to 700 kVAr
Sunny Central 630CP-JP
0 kVAr to 880 kVAr
Sunny Central 800CP-JP
0.5 to 1
The parameter should not fall be-
low 0.8 in normal operation.
SMA Solar Technology AG
Default
value
220 kVAr
310 kVAr
385 kVAr
0 kVAr
0 kVAr
0 kVAr
150 kVAr
210 kVAr
264 kVAr
0.9
System Manual

Advertisement

Table of Contents
loading