General Data
Operating temperature range
Self-consumption in operation**
Standby consumption***
Internal auxiliary supply voltage
Maximum permissible value for relative humidity (non-
condensing)
Maximum operating altitude above mean sea level
Maximum operating altitude above MSL for option "In-
stallation at high altitudes"
Fresh air consumption**
Degree of protection of medium-voltage compartment as
per IEC 60529
Degree of protection of transformer compartment and in-
verter compartment as per IEC 60529
* optional
** information based on inverter
*** separated according to consumption of the inverter and standby power losses of the transformer
15.6

MV Power Station 1600SC-JP

DC Input
MPP voltage range at +25°C
MPP voltage range at +50°C
Maximum input current
Number of independent MPP inputs
Number of DC inputs
AC Output
AC power at +25°C*
AC power at +40°C*
AC power at +50°C*
Nominal AC voltage
Optional nominal voltages
AC power frequency
Maximum total harmonic distortion
Maximum output current at 20 kV
System Manual
−25°C to +40°C / −25°C to +55°C*
< 3800 W
< 200 W + 950 W
230 V / 400 V (3/N/PE), 50 Hz / 60 Hz
15% to 95%
1000 m
1001 m to 2000 m / 2001 m to 3000 m
3
6000 m
/h
IP23D
IP00
641 V to 850 V
583 V to 850 V
2 x 1400 A
2
18
1760 kVA
1664 kVA
1600 kVA
20 kV
10 kV to 13 kV
50 Hz / 60 Hz
< 3 %
51 A
MVPS22JP-SH-en-11
15 Technical Data