12.6.2 Connecting the Cable Shield Using a Shield Clamping Saddle

1. Remove the shield clamping saddle from the busbar.
2. Press the shield clamping saddle down onto the shield of the
stripped cable until it snaps into place and fasten hand-tight.
12.7

Entering the Password via the Touch Display

Installer access
The "Installer" access level is activated by entering the installer password. The access level is reset after 15
minutes.
Procedure:
1. Select
.
2. Select
.
3. Confirm your entry by selecting
☑ The
symbol appears in the status info line.
12.8

Settings on the User Interface of the Inverter

12.8.1 Logging Into the User Interface

Default network settings for the service interface
IP address:
192.168.100.2
Subnet mask:
255.255.255.0
Password for the user groups "installer" and "user": sma
Identical passwords for the user groups
If your "user" password is the same as your "installer" password, you will automatically be logged in as an
installer.
Requirement:
☐ JavaScript must be enabled in your web browser (e.g. Internet Explorer).
Procedure:
1. Connect the laptop to the service interface of the inverter.
2. Start your web browser.
System Manual
.
12 Periodic Actions
MVPS22JP-SH-en-11
177