Programming for the Video Alarm Verification

Program the 4204 relays as follows:
Device Type = 4
Relay Type = 1 (ECP)
ECP Address = (module's device address)
Relay Number = (actual relay number used on the
module)
Relay "A" (kissoff):
action = 1 (closed for 2 seconds)
start zone type = 60 (alarm verification)
stop zone type = 60 (alarm verification)
Relay "B" (hold the line):
action = 2 (stay closed)
start zone type = 60 (alarm verification)
stop zone type = 57 (yyy seconds set in field 1*75; set
to 6 sec.)
Relay "C" (camera):
action = 1 (closed for 2 seconds)
start event = 1 (alarm)
start zone list = "n" (zone list number containing
camera zones for this relay)
4-10
Data Field Programming
*30 = (Multifrequency dialing)
*33 = primary phone number
*41 = 0 (use EOLR)
*45 = 1 (Contact ID)
*81 = enable cancel reports in order to send
verification code (9
*84 = 00 (intermittent sensor disabled)
1*66 = 0 (disable silence of sounders during video
alarm verification operation)
1*67 = 1 (must also be selected to assure that
Contact ID report Event 609 will be
transmitted to the monitoring location after
the alarm transmission.)
1*75 = 006 (6 seconds)
NOTE: A zone list must be programmed which
contains all zones protected by the camera being
triggered by the "camera" relay.