Prevent Fire Timeout
*21
0 = disable (timeout)
1 = enable (no timeout)
Keypad Panic Enables (partition-
*22
specific)
0 = disable
1 = enable
Multiple Alarms (partition-specific)
*23
0 = disable
1 = enable
Ignore Expansion Zone Tamper
*24
0 = disable (tamper detection)
1 = enable (no tamper detection)
Burglary Trigger for Response Type
*25
8
0 = disable
1 = enable
Intelligent Test Report
*26
0 = disable
1 = enable
Test Report Interval
*27
Enter 001-999 for the test report interval in
hours.
Enter 000 for test reporting.
Power-Up in Previous State
*28
0 = disable
1 = enable
Quick Arm (partition-specific)
*29
0 = disable
1 = enable
Multifrequency or Pulse Dial
*30
0 = pulse
1 = multifrequency
If you select multifrequency, make sure the subscriber has requested and is paying for multifrequency service. Note
that whether or not multifrequency dialing for call placement is permitted, communication by the use of DTMF
signaling (ADEMCO High Speed, 4 + 2 Express, ADEMCO Contact ID) will still take place. See field 1*33 for
Multifrequency w/decadic dial pulse backup
PABX Access Code
*31
Enter 00-09; B-F (11-15)
FIELD
TITLE and DATA ENTRIES
If enabled, there is no timeout of the alarm sounder duration for all fire zones,
regardless of partition, so that fire sounding continues until the system is
reset.
If disabled, (timeout) the normal burglary sounder duration (field ✳13) applies
to fire alarms.
If enabled, the keypad panics (zones 995, 996, and 999) may be used in this
partition. There are 3 entries in this field, one for each panic.
If enabled, allows more than one alarm sounding for a given zone during an
armed period.
NOTE: that multiple alarm soundings will not occur more frequently than
allowed by the programmed alarm sounder duration. This has no impact on
the number of communication messages transmitted.
If disabled, the system monitors the tampers on expansion zones.
NOTE: Only applicable to certain polling loop sensors with tamper switches or
5800 Series transmitters.
If enabled, allows triggering of the voltage output on Pin 3 of the J7 header to
include zone response type 8 (24-hr. auxiliary).
If enabled, no test report is sent if any other type of report was sent since the
last test report.
If disabled, test reports are sent at the set intervals, regardless of whether or
not any other report has been sent..
If a test report is desired, enter a test code in field *81 and *82. Set first test
report time in field *83.
If enabled, the system, upon power-up, reverts to its status prior to a complete
power loss.
If disabled, the system always powers up in a disarmed state.
NOTE: Neither authority level 0 nor 5 can be used to disarm the system if the
control powers up armed.
If enabled, allows arming of the burglary system in AWAY, STAY, INSTANT,
or MAXIMUM mode by using the [#] key instead of the user code.
When armed, the system reports closing as User 0 if Open/Close reporting for
User #2 (typically a Master level user) was enabled for a given partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes cannot
disarm the system.
Select the dialing method for the system
This field is used to enter up to four 2-digit numbers representing the prefix
needed to obtain an outside telecom line. If not required, enter nothing and
proceed to next field.
EXPLANATION
Section 5 - Data Field Descriptions
5-3