VISTA-120 Installation and Setup Guide
Primary Subscriber's Account
*32
Number (partition-specific)
Enter 00-09; B-F (11-15)
Primary Phone Number
*33
Enter 0-9; #11 for *, #12 for #, #13 for a 2-
second pause.
Secondary Phone Number
*34
Enter 0-9; #11 for *, #12 for #, #13 for a 2-
second pause.
Download Phone Number
*35
Enter 0-9; #11 for *, #12 for #, #13 for a 2-
second pause.
Download ID Number
*36
Make entries as 2-digit numbers as follows:
00=0 01=1
06=6 07=7
12=C 13=D 14=E 15=F
Download Command Enables
*37
0 = disable
1 = enable
Prevent Zone XXX Bypass (partition-
*38
specific)
Enter a zone number (001-128).
Enter 000 if all zones can be bypassed.
Enable Open/Close Report for
*39
Installer Code (partition-specific)
0 = disable
1 = enable
Enable Open/Close Report for
*40
Keyswitch
0 = disable
1 = enable
Normally Closed or EOLR (Zones 2-
*41
8)
0 = EOLR used
1 = normally closed
Suppress Fire Relay
*42
0 = disable
1 = enable
FIELD
TITLE and DATA ENTRIES
5-4
02=2
03=3
04=4
05=5
08=8
09=9
10=A 11=B
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. Each number requires a 2-digit entry so as to allow entry of
hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data
only in the first 3 locations, and enter * in the fourth location.
Enter the primary central station phone number, up to 17 digits. This is the
phone number the control will use to transmit Alarm and status messages to
the central station. Do not fill unused spaces.
NOTE: Backup reporting is automatic only if a secondary phone number is
entered.
Enter the secondary phone number, up to 17 digits. The secondary phone
number is used if communication on the primary number is unsuccessful, or if
split/dual reporting is desired. Do not fill unused spaces.
NOTE: If this field is programmed, a secondary subscriber account number
(field *90) must also be programmed.
Enter the downloading phone number, up to 17 digits. Do not fill unused
spaces.
NOTE: This field is applicable only if downloading is utilised.
Enter eight digits.
NOTE: This field is applicable only if downloading is utilised.
Enabling a function means that you are able to perform that function via the
ADEMCO Compass Downloading software.
Functions are as follows: Dialler Shutdown; System Shutdown; Restrict
Access*; Remote Bypass; Remote Disarm; Remote Arm; Upload Program;
Download Program.
*Restrict download access when the system is armed: can only arm unarmed
partitions, upload program/event log, command relays and request status.
Enter three digits for zone that cannot be bypassed by the user.
This selection does not affect fire zones, which the system prevents from
being bypassed.
If enabled, whenever the Installer Code is used to arm or disarm the partition,
an open/close report is sent to the central station.
If enabled, whenever the keyswitch is used to arm or disarm the partition, an
open/close report is sent to the central station.
If 0, end-of-line resistors must be used on zones 2-8.
If 1 end-of-line resistors cannot be used and only normally closed devices
must be used.
If enabled, the system does not activate 4204/Powerline Carrier Device for fire
alarms.