VISTA-120 Installation and Setup Guide
Entry Errors
If an address is improperly entered, the keypad
displays "FC."
If a program entry is improperly entered (for
example, a larger number than is permitted), the
keypad display will go blank.
In either of the above cases, simply re-enter [✴] + the
correct field number and then enter the correct data.
Programming System-Wide Data Fields
Values for some programming fields are system-wide
(global), and some can be different for each partition
(partition-specific).
The partition-specific programming fields are
automatically skipped when programming the
global fields. If the system has only 1
partition, the partition-specific fields are not
automatically skipped.
To program system-wide data fields, perform the
following steps:
1
Enter Program Mode: Installer Code + 8 0 0 0.
The following display appears:
Program Mode
✳ Fill # View – 00
2
If the control has not been programmed before,
enter ✳97 to load factory defaults.
3
Press [✳] and enter the first field number to be
programmed (for example, ✳00, Installers Code).
Make the desired entry. When the field is
complete, the keypad beeps three times and
advances to the next field. If you do not want to
change the next field, press [✳] and enter the next
field number to be programmed.
First Page of fields
(✳00 - ✳90)
To change to the next page of fields, press ✳94. To
return to the previous page of fields, press ✳99.
Press ✳99 or ✳98 to exit Program Mode.
4

#93 Menu Mode Programming

The #93 Menu Mode is an interactive mode through which much of the system's programming is done. In this mode,
there are "question and answer" prompts that can be accessed once Data Field Program Mode has been entered. These
prompts require a 2-line alpha keypad.
Refer to the VISTA-120 Programming Guide for detailed procedures for #93 Menu Mode Programming.
The following is a list of the main menu selections.
MAIN MENU
ZONE PROG?
1 = YES 0 = NO
0
4-2
OPTIONS
For programming the following:
Zone Number
Zone Response Type
Partition Number for Zone
Dialler report code for zone
Input Device Type for zone (whether RF, polling loop, etc.)
Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.
NOTE: If the number of digits that you enter in a data
field is fewer than the maximum permitted (for
example, a phone number), the keypad displays the last
entry and waits. To proceed, enter [✴] + the next data
field you wish to program.
Programming Partition-Specific Data Fields
To program partition-specific data fields once in
Program Mode, do the following:
1.
Enter Program Mode: Installer Code + 8 0 0 0.
Press ✳91, which will prompt you for the partition
2.
number desired.
Enter a partition-specific field number (e.g., ✳09) to
3.
begin programming.
When the first field's entry is completed, the next
partition-specific field is automatically displayed.
When all partition-specific fields are programmed,
the system returns to the global programming
fields (page 1 fields).
4.
Repeat this procedure for each partition in the
installation.
NOTE: To return to the global program fields before
finishing all fields, enter any global field number.
Programming Partition-Specific Fields
Press ✳91 to select a partition.
Enter the partition to be programmed.
Enter a partition-specific field number and make
After partition-specific fields are programmed,
press ✳91 to select next partition.
Enter any global field number to return to the
global fields at any time.
↓ ↓ ↓ ↓
↓ ↓ ↓ ↓