Cable Specifications; Control Input/Output And Control Data - Danfoss VLT DriveMotor FCP 106 Design Manual

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Specifications
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Maximum ambient temperature at reduced performance
Temperature during storage
Temperature during transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Safety standards
EMC standards, emission
EMC standards, immunity
Energy efficiency class, VLT
Energy efficiency class, VLT
1) The stated IP and Type rating only apply when the FCP 106 is mounted on a wall mount plate or a motor with the adapter
plate. Ensure that the gasket between the adapter plate and the motor has a protection rating corresponding to the required
6
6
rating for the combined motor and frequency converter. As standalone frequency converter, the enclosure rating is IP00 and
Open type.
2) Determined according to EN50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.

6.6 Cable Specifications

Cable lengths and cross-sections
Maximum motor cable length for wall mount kit, screened/armored
Maximum cross-section to motor, mains for MH1–MH3
Maximum cross-section DC terminals on enclosure type MH1–MH3
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Minimum cross-section to control terminals
Maximum cross-section to thermistor input (at motor connector)

6.7 Control Input/Output and Control Data

Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Voltage level, logic 0 NPN
Voltage level, logic 1 NPN
Maximum voltage on input
Input resistance, R
Digital input 29 as pulse input
Analog inputs
Number of analog inputs
Terminal number
Terminal 53 mode
Terminal 54 mode
Voltage level
Input resistance, R
68
VLT
®
DriveMotor FCP 106
®
DriveMotor FCM 106
i
i
Danfoss A/S © 06/2016 All rights reserved.
®
DriveMotor FCP 106/FCM 106
EN 61000-3-2, EN 61000-3-12, EN 55011, EN 61000-6-4
2)
Maximum frequency 32 kHz push-pull-driven and 5 kHz (O.C.)
Parameter 6-19 Terminal 53 mode: 1=voltage, 0=current
Parameter 6-29 Terminal 54 mode: 1=voltage, 0=current
50 °C (122 °F)
-25 to +65 °C (-13 to +149 °F)
-25 to +70 °C (-13 to +158 °F)
1000 m (3280 ft)
3000 m (9842 ft)
EN/IEC 60204-1, EN/IEC 61800-5-1, UL 508C
EN 61800-3, EN 61000-6-1/2
4 mm
4 mm
2.5 mm
2.5 mm
0.05 mm
4 mm
Approximately 4 kΩ
Approximately 10 kΩ
-10 °C (14 °F)
-20 °C (-4 °F)
IE2
IES
2 m (6.56 ft)
2
/11 AWG
2
/11 AWG
2
/13 AWG
2
/13 AWG
2
/30 AWG
2
/11 AWG
4
18, 19, 27, 29
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
2
53, 54
0–10 V
MG03M202